LPJ-100SP
-
Ultimate Protection 600Vac/300Vdc, 1-600A, Dual Element, Time-Delay Fuses
Class J dual element, current-limiting, time-delay fuses available with optional open fuse indication on select ratings (see data sheets).
Time-delay – 10 seconds (minimum) at 500% of rated current.
__________________________________________________________________________
Available With Indication
Description:
Dual-element, time-delay fuse; 10 seconds (minimum) at 500% rated amps. Now available with optional indication on select ratingsRatings:
Volts: 600Vac (or less); 300Vdc (or less)
Amps: 1-600A
IR: 300kA RMS Sym. 100kA dc
Agency Information: CE, UL Listed - Special Purpose*, Guide JFHR, File E56412, CSA Certified (200k AIR) Class J per CSA-22.2 No. 248.8, Class 1422-02, File 53787.
General Information:
• True dual-element fuses with a minimum 10 second timedelay at 500% overload.
• Long time-delay minimizes needless fuse openings due to temporary overloads and transient surges.
• Can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail.
• High interrupting rating to safely interrupt overcurrents up to 300,000A.
• High degree of current limitation due to the fast speed-ofresponse to short-circuits.
• Faster response to damaging short-circuit currents than mechanical overcurrent protective devices.
• Reduces let-through thermal and magnetic forces in order to protect low withstand rated components.
• Proper sizing provides “no damage” Type “2” coordinated protection for NEMA and IEC motor control in accordance with IEC Standard 947-4-1.
• Dual-element fuses have lower resistance than ordinary fuses so they run cooler.
• Lower watts loss reduces power consumption.
• Unique dimensions assure that another class of fuse with a lesser voltage rating, interrupting rating or current-Iimiting ability cannot be substituted.
• Space-saving package for equipment down sizing.Features and Benefits
• Separate overload and short-circuit elements provide time delay for sizing of high inrush loads linked with Class J current limitation.
• Selective coordination ratio of 2:1 (within Low-Peak fuse family) prevents electrical shutdowns from extending beyond the failed circuit.
• Series combination ratings with branch circuit breakers allows broad range of coverage, independent of breaker manufacturer.Typical Applications
• Power Panelboards
• Branch Circuit Breaker Panelboard Mains
• Machinery Disconnects
• Industrial ControlCatalog Numbers (Amps)
Catalog numbers Amp rating Catalog numbers Amp rating LPJ-1SP 1A LPJ-25SP** 25A LPJ-1-1/4SP 1.25A LPJ-30SP** 30A LPJ-1-6/10SP 1.6A LPJ-35SP** 35A LPJ-1-8/10SP 1.8A LPJ-40SP** 40A LPJ-2SP 2A LPJ-45SP** 45A LPJ-2-1/4SP 2.25A LPJ-50SP** 50A LPJ-2-1/2SP 2.5A LPJ-60SP** 60A LPJ-2-8/10SP 2.8A LPJ-70SP** 70A LPJ-3SP 3A LPJ-80SP** 80A LPJ-3-2/10SP 3.2A LPJ-90SP** 90A LPJ-3-1/2SP 3.5A LPJ-100SP** 100A LPJ-4SP 4A LPJ-110SP** 110A LPJ-4-1/2SP 4.5A LPJ-125SP** 125A LPJ-5SP 5A LPJ-150SP** 150A LPJ-5-6/10SP 5.6A LPJ-175SP** 175A LPJ-6SP** 6A LPJ-200SP** 200A LPJ-7SP** 7A LPJ-225SP** 225A LPJ-8SP** 8A LPJ-250SP** 250A LPJ-9SP** 9A LPJ-300SP** 300A LPJ-10SP** 10A LPJ-350SP** 350A LPJ-12SP** 12A LPJ-400SP** 400A LPJ-15SP** 15A LPJ-450SP** 450A LPJ-17-1/2SP** 17.5A LPJ-500SP** 500A LPJ-20SP** 20A LPJ-600SP** 600A *Meets all performance requirements of UL Standard 248-8 for Class J fuses.
**Available with optional permanent replace fuse indication. To order, place “I” at end of catalog number. As below table.
Catalog Numbers (With optional permanent replace fuse indication)
LPJ-6SPI LPJ-35SPI LPJ-150SPI LPJ-7SPI LPJ-40SPI LPJ-175SPI LPJ-8SPI LPJ-45SPI LPJ-200SPI LPJ-9SPI LPJ-50SPI LPJ-225SPI LPJ-10SPI LPJ-60SPI LPJ-250SPI LPJ-12SPI LPJ-70SPI LPJ-300SPI LPJ-15SPI LPJ-80SPI LPJ-350SPI LPJ-17-1/2SPI LPJ-90SPI LPJ-400SPI LPJ-20SPI LPJ-100SPI LPJ-450SPI LPJ-25SPI LPJ-110SPI LPJ-500SPI LPJ-30SPI LPJ-125SPI LPJ-600SPI