COOPER BUSSMANN (EATON‘S)

BUSSMANN PVS-R系列快速熔断器

 

 

   PVS-R 系列产品型录

   PVS-R 系列产品型录

  PVS-R 系列产品型录

 

 

PVS-R RK5 PV fuses

600Vdc fast-acting, current-limiting RK5 fuses designed for protecting photovoltaic systems in ratings from 20 to 400 amps.

 

 

Description:
A range of UL 2579 fast-acting 600Vdc Class RK5 fuses specifically designed to protect solar power systems in extreme ambient temperature, high cycling and low level fault current conditions (reverse current, multi-array fault).

 

• Listed to UL 2579 – The Industry’s Only Class R Photovoltaic Fuse

• Specially Designed to Protect in Lower-Level Overload Regions where Common Time-Delay Fuses Do Not

• Demonstrated Performance in Extreme Temperatures, Ranging from -40°C through 90°C

• Proven Application in Constantly Changing PV Environmental Conditions

• Easily Applied in Readily Available Class R Fuse Blocks and Disconnects
 

User Benefits

• Maximize uptime and reliability using the only fuse designed and listed to UL 2579: Low Voltage Fuses – Fuses for Photovoltaic Systems.

• Minimize chances of equipment failure and personnel injury when using full range fuses having the industry’s fastest response time to low-magnitude faults.

• Maximize return on investment with fuses proven to withstand harsh temperatures.

• Minimize design time, operating outage time and replacement costs with fuses qualified in excessively changing environmental conditions.

• Simplify compatibility with readily available industry standard Class R fuse blocks and disconnects.

 

Ratings:

Volts: 600Vac to UL 248-12; 600Vdc to UL 2579

Amps: 20-350A

IR: 200kA RMS Sym. AC;20kA DC (20-60A);10kA DC (70-350A)
 

Agency Information:
UL Std. 248-12, Class RK5, UL Listed, Guide JFGA, File E335324. Photovoltaic to UL 2579, CSA Component Certified C22.2.
 

Features and Benefits

• Current limitation for non-inductive circuits provides Class RK5 current-limiting response to ground fault and short-circuit conditions.

• Designed for the protection and isolation of photovoltaic systems.
 

Typical Applications

• Photovoltaic systems

• Inverters

 

Catalog Numbers (Amps)

PVS-R-20 PVS-R-40 PVS-R-80 PVS-R-150 PVS-R-250
PVS-R-25 PVS-R-50 PVS-R-90 PVS-R-175 PVS-R-300
PVS-R-30 PVS-R-60 PVS-R-100 PVS-R-200 PVS-R-350
PVS-R-35 PVS-R-70 PVS-R-125 PVS-R-225  

 

Performance Characteristics
Temperature Derating: Designed to maximize rated capacity in elevated environmental temperatures.

Overload Protection: Proven to clear faults faster than the UL requirement.

Power Loss: Minimal energy consumption leading to increased efficiency

Catalog
Number
Amp
Rating
Power Loss (Watts)
0.8 x In 1.0 x In
PVS-R-30 30A 2.3 4.0
PVS-R-60 60A 5.0 8.8
PVS-R-100 100A 7.6 13.6
PVS-R-200 200A 19.7 28.5
PVS-R-350 350A 24.6 43.5

n = Rated current.


Carton Quantity and Weight

 

Amp Ratings Carton Qty. Weight Per Carton
Lbs. Kg.
20–30 10 1.45 0.658
35-60 10 3.35 1.520
70–100 1 0.40 0.181
125–200 1 1.08 0.490
225-350 1 2.25 1.021

 

 

 

 

 

 

系列:PVS-R系列快速熔断器

电压:600Vac

电流:20-400A

分段容量:200kA RMS Sym.

认证:UL、CE、CSA