TCF系列 Class J 600Vac 延时模块熔断器
Low-Peak CUBEFuse Finger-Safe, Dual-Element, Time-Delay Class CF Fuse, 1-100A, 600Vac/300Vdc
Catalog Symbols: TCF_ Indicating fuse (6-100A)
TCF_RN Non-indicating fuse (1-100A)
Dual-Element, Time-Delay Fuse: 10 Seconds Minimum Operating Time at 500% Rated Current
Ratings:
Volts –600Vac/300Vdc
Amps –1 to 100A
IR –300kA RMS Sym. (UL)
–200kA RMS Sym. (CSA)
–100kA DC (UL & CSA)
Agency Information:
• UL Listed Fuse: Guide JFHR, File E4273
• CSA Certified Fuse: Class 1422- 02, File 53787
• CE compliance for the European Union low voltage directive
• RoHS Compliant
Other Ratings/Specifications:
Watts Loss at rated current: TCF30: 3.99W
TCF60: 6.23W
TCF100: 9.51W
Operating and Storage Temperature Range: -40 to 80°C
Material Specifications:
• Case: Glass filled PES (Polyethersulfone)
• Terminals: Copper alloy
• Terminal plating: Electroless tin
• Indicator lens: PES (Polyethersulfone) (indicating version only)
• Indicator: Energetic chemical
Fuse Catalog Numbers Indicating (Amps) |
|||
TCF6 |
TCF25 |
TCF50 |
TCF100 |
TCF10 |
TCF30 |
TCF60 |
|
TCF15 |
TCF35 |
TCF70 |
|
TCF17-1⁄2 |
TCF40 |
TCF80 |
|
TCF20 |
TCF45 |
TCF90 |
Fuse Catalog Numbers Non-Indicating (Amps) |
|||
TCF1RN |
TCF17-1⁄2RN |
TCF40RN |
TCF80RN |
TCF3RN |
TCF20RN |
TCF45RN |
TCF90RN |
TCF6RN |
TCF25RN |
TCF50RN |
TCF100RN |
TCF10RN |
TCF30RN |
TCF60RN |
|
TCF15RN |
TCF35RN |
TCF70RN |
Fuse Holder Catalog Numbers |
|||
Catalog Numbers |
Amp Range |
Wire Range*Single Wire |
Dual Wire |
TCFH30N |
1-30 |
14 To 8 AWG Cu |
18 to 10 AWG |
TCFH60N |
1-60 |
14 To 4 AWG Cu |
10 to 6 AWG Cu |
TCFH100N |
1-100 |
10 To 1 AWG Cu |
6 AWG Cu |
Features and Product Benefits
• The world’s first finger-safe power fuse system.
• Smallest footprint of any class fuse including Class J, CC, T and RK.
• Meets Class CF and Class J time-delay electrical performance requirements.
• Available with and without open fuse indication.
• The indicating version features easyID™ open fuse technology for faster troubleshooting and reduced downtime.
• Faster response to damaging faults to help reduce destructive thermal and magnetic forces.
• True dual-element fuse construction with a minimum of 10 seconds timedelay at 500% of rating.
• Long time-delay minimizes nuisance circuit openings due to temporary overloads and transient surges.
• High interrupting rating to safely interrupt faults up to 300kA.
• No venting of arc or molten metal and gases during opening.
• Robust cycling and inrush current withstand.
• Low let-through currents under fault conditions.
• Provides Type 2 “No Damage” protection for IEC motors starters when properly sized.
• Easy selective coordination with any other Cooper Bussmann Low-Peak Class CC, L, J and RK1 fuse with simple 2:1 amp ration between upstream and downstream fuses.