COOPER BUSSMANN (EATON‘S)

NON系列 Class K5 H 250Vac 通用非限流熔断器

250 V NON/600 V NOS Class K5 and H fuses

 

Description

Basic protection 250V NON Class K5 and H general purpose, non-current-limiting, one-time fuses.

Catalog symbol : NON-(amp)

 

Ratings

Volts

  • 250 Vac

  • 125 Vdc (1/8-100 A)

Amps  : 1/8-600 A

IR

  • 50 kA Vac RMS Sym. (1/8-60 A)

  • 10 kA Vac RMS Sym. (65-600 A)

  • 50 kA Vdc (1/8-60 A)

  • 10 kA Vdc (65-100 A)

 

Agency information

  • UL Listed, Class K5 (1/8-60 A), Std. 248-9, Class H (65-600 A), Std. 248-6 (125 Vdc 1/8-100 A), UL Guide JDDZ, File E4273

  • CSA Certified, Class 1421-01, File 53787 (1/8-12 A, 65-600A)†

  • CE

  • † For CSA Certified 15-60 A, see PON data sheet no. 4126

 

Catalog numbers (amps)

NON-1/8

NON-3

NON-12

NON-65

NON-200

NON-1/2

NON-3-2/10

NON-15

NON-70

NON-225

NON-3/4

NON-4

NON-20

NON-75

NON-250

NON-8/10

NON-5

NON-25

NON-80

NON-300

NON-1

NON-6

NON-30

NON-90

NON-350

NON-1-1/4

NON-6-1/4

NON-35

NON-100

NON-400

NON-1-1/2

NON-7

NON-40

NON-110

NON-450

NON-1-6/10

NON-8

NON-45

NON-125

NON-500

NON-2

NON-9

NON-50

NON-150

NON-600

NON-2-1/2

NON-10

NON-60

NON-175

 

 

Carton Quantity

Amp  Rating

Carton Qty.

1/8-60

10

65-100

5

110-600

1

 

Features

  • Protect lighting, heating and other circuits not subject to temporary surges and where available short-circuit currents are relatively low

  • NON one-time fuses do not have any appreciable degree of timedelay and thus should not be specified in circuits where large transients or motor overloads occur. Use Bussmann series advanced protection FUSETRON™ FRN-R or ultimate protection Low-Peak™ LPN-RK dual-element, time-delay fuses.

  • For general purpose circuits, size at amp rating of circuit

  • For motor circuits, size at 300% to 400% according to the NEC® motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)

 

Recommended fuse blocks :

  • 1-, 2- and 3-pole modular fuse blocks up to 600 amps — see data sheet no. 10487

  • 1-, 2- and 3-pole modular power distribution fuse blocks up to 60 amps — see data sheet no. 10490

 

Fuse reducers for Class R fuses :

Equipment fuse clips

Desired fuse (case)

Catalog no. (pairs)

size

250V

60A

30A

NO.263

100A

30A

NO.213

60A

NO.216

200A

60A

NO.226

100A

NO.2621

400A

100A

NO.2641+

200A

NO.2642

600A

100A

NO.2661+

200A

NO.2662+

400A

NO.2664+

† Not CSA certified.

For additional information on Class K5 & H fuse reducers, see data sheet no. 1118.

 

系列 :  NON/NOS系列 一次性一般用途限流熔断器,Class K5
电流 :1/8-600 A
电压 :
- 250 Vac
- 125 Vdc (1/8-100 A)
分段容量 : 
- 50 kA Vac RMS Sym. (1/8-60 A)
- 10 kA Vac RMS Sym. (65-600 A)
- 50 kA Vdc (1/8-60 A)
- 10 kA Vdc (65-100 A)
认证 : UL CSA CE